The 350 W AT-FR rack type panel is installed in a standard 19" cabinet and acts as the main host of a fire emergency broadcasting system. By connecting to a fire alarm linkage controller, output modules, constant-voltage speakers and expansion amplifiers, it delivers powerful voice evacuation for medium-size commercial and industrial buildings.
On receiving an emergency signal, the panel switches automatically to emergency broadcasting and plays pre-recorded fire evacuation messages or live MIC announcements, guiding people to safe exits.
Rack type 1U fire emergency voice control panel, 350 W high-power output
120 VAC constant-voltage speaker line for wide-area coverage
Four broadcasting modes: EMER Radio, MIC paging, USB / MP3 and AUX audio input
Emergency message import via MIC or USB (up to 30 s)
30-minute loop recording of operations and broadcasts
Automatic fault monitoring of speaker line, mains and backup power with audio and visual alarm
Overload protection for reliable long-term operation
Optional communication module for integration with fire linkage controllers and BMS
Intelligent air-cooled design for stable 350 W continuous output
Compatible with rack expansion amplifiers via signal port
Working Environment
Ambient temperature: 0 °C to 40 °C
Relative humidity: ≤ 95% RH, non-condensing
Electrical
Mains input: AC 187 V to AC 242 V
Speaker output: 120 VAC constant-voltage line
Rated output power: 350 W
Approx. rated output current: 2.9 A
Frequency response: 80 Hz to 8 kHz (±3 dB)
Harmonic distortion: ≤ 5%
Signal-to-noise ratio: ≥ 70 dB
Recording
Recording time: 30 minutes loop recording
Mechanical
Installation: 19" cabinet, 1U panel type
Dimensions: 482.6 mm × 188.0 mm × 44.0 mm